1.0 InstructionThe CHZ4(T)-12(15/27/38) KV/630A-1250A Providing the
features of a traditional re-closer, plus the bene of up to date
design optimized for automation, remote control and monitoring, now
or in the future.by customer demand for improved return on capital
investment in the distribution network to achieve optimum
performance and reliability, making use of the latest available
technology in insulation, vacuum interruption and
microelectronics. Three phase pole-top automatic circuit
re-closer are designed and produced by the three kind of
international advanced technology, as epoxy solid encapsulated
technology, permanent magnetic actuating device, and intelligence
control technology and so on.The product is composite with solid
dielectric insulted pole, permanent magnetic actuating device or
motor actuating device, control unit, current transformer and
vacuum interrupter and voltage sensor. Except the control unit is a
single device, the others are combined together, compact frame,
flexible design, easy to operate. The CHZ4(T)-12(15/27/38)
KV/630A-1250A three phase pole-top automatic circuit re-closer is
for 12kV(15KV/27KV/38KV),50/60Hz distribution system, has not only
circuit breaker control and protection features, but also can
automatically detect the lines running statement.Once the load side
line or equipment occur a fault, meet or exceed current setting the
minimum starting current, it will be good at a per-determined
action sequence, to identify the fault is transient or permanent,
and auto-complete one to three re-closing.2.0 Designing
Standard2.0.1 ANSI-IEEE-Std-C37.60-2003,2.0.2 BS EN
60529-1992+A2:20132.0.3 IEEE Std.C37.60-2013, IEEE Std
C57.12.29-20142.0.4 JB7570-1994, and DL/T813-20022.0.5 IEC56,
IEC694, IEC62271-1113.Specification for Vacuum Circuit
Breaker 3.1
Ratings for ZW32-12(15) KV Vacuum Circuit BreakerNo.ItemUnitData
for ZW32-12KVData for ZW32-15KV1Rated VoltageKV12152Rated
insulation level(phase to ground, phase to phase)1 min Frequency
withstand voltageDryKV4250Wet3445Lighting Impulse Withstand
Voltage(Peak)KV751103Medium Interruption:Vacuum4Medium
isolation:Solid polymer5Mechanism of operation (closing and
shot):Magnetic6Assembly:Suitable weather for
substation7Environmental operating temperature:FROM
-40ºC-+50ºC8Position indicator: Green-closed; Open-red9Minimum
distance of contouring of the insulationMM40060010Rated
FrequencyHz50/6011Rated CurrentA630/800/125012Rated Min Start-up
CurrentNumericalAadjustablePermissible deviation%±1013Rated Fault
Interrupter CapacityKA/3s12.5/2014Rated Fault Symmetrical Making
CurrentKA12.5/2015Rated Short-Time Withstand
CurrentKA12.5/2016Rated Peak Withstand
CurrentKA12.5/2017Interrupting Time(Max) (Cycle)sNo more than
418The conditions of different phase earthed fault short-circuit
breaking currentKA17.319Rated Cable Charging Breaking
currentA2520Rated Operating
Sequence O-0.1s-CO-2s-CO-2s-CO-C21Rated Operation
VoltageVAC/DC110/125/220/24022Rated Short-Circuit Current Breaking
TimesTime 90%~100% Rated Short-Circuit Current volume1645%~55%
Rated Short-Circuit Current volume4415%~20% Rated Short-Circuit
Current volume5623Mechanical Life (Mechanical stability)Time/Unit
Operation1500024Current TransformerPrimary Rated
CurrentA600/1000Secondary Rated Current1 or 5Accuracy
GradeCL0.2/5P20CapabilityVA1525Special Manual Closing
Mechanism optional26Earthing Solidly
Earthed 3.2
Ratings for ZW32-27(38) KV Vacuum Circuit
Breaker No.ItemUnitData for ZW32-27KVData for ZW32-38KV1Rated
VoltageKV27382Rated insulation level (phase to ground, phase to
phase)1 min Frequency withstand voltageDryKV6595Wet5080Lighting
Impulse Withstand Voltage(Peak)KV145/1501853Medium
Interruption:Vacuum4Medium isolation:Solid polymer5Mechanism of
operation (closing and shot):Magnetic6Assembly:Suitable outdoor for
substation or pole mounted7Environmental operating temperature:FROM
-40ºC-+50ºC8Position indicator: Green-closed; Open-red9Minimum
distance of contouring of the insulationMM68090010Rated
FrequencyHz50/6011Rated CurrentA200A/400A/630A/1250A12Rated Min
Start-up CurrentNumericalAAdjustablePermissible
deviation%±1013Rated Fault Interrupting CapacityKA/3S12.5/2014Rated
Symmetrical Making CurrentKA12.5/2015Rated Short-Time Withstand
CurrentKA12.5/2016Rated Peak Withstand
CurrentKA12.5/2017Interrupting time(Max)(Cycle)SNot more than
4 18The conditions of different phase earthed fault
short-circuit breaking currentKA12.52019Rated Cable Charging
Breaking currentA2520Rated Operating
Sequence O-0.1s-CO-2s-CO-5s-CO-C21Rated Operation
VoltageVAC/DC110/125/220/24022Rated Short-Circuit Current Breaking
TimesTime 90%~100% Rated Short-Circuit Current
volume 16 45%~55% Rated Short-Circuit Current
volume 44 15%~20% Rated Short-Circuit Current
volume 5623Mechanical Life (Mechanical stability)Time/unit
Operation1000024Current TransformerPrimary Rated
CurrentA600/1000 Secondary Rated Current 1 or
5 Accuracy
GradeCL0.25/5P20 CapabilityVA1525Special
Related products about 15kv/27kv/38kv Recloser Wtith IEC61850 and DNP3.0 for Distribution and Substation
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup