Three Phase UPS High Frequency UPS Modular UPS Power Supply 20kVA to 600kVA for Data Center

Main feature1.Hot-swappable design2.Battery cold function3.Intelligent fan control and redundant design4.Parallel system expansion up to 4 units5.SNMP adapter ,dry contact,RS485(optional)6.Fully DSP control and high reliability and performance7.Allow 100% unbalanced load8.7 inch touchable LCD screenApplication1.Data center 2.Telecom system3.IT room4.Financial centerSpecificationModule ModelGM30Module Capacity30KVAInput/Output WayThree phase in three phase outModule Dimension(W*D*H)mm440*590*130Weight(kg) 32 kgInput PF≥0.99Input Total Harmonic Distortion THDI(%)≤3%Model3RWG90KM303RWG150KM303RWG180KM303RWG240KM303RWG270KM30Capacity 90KVA 150KVA 180KVA 240KVA 270KVA Type of power moduleGM30Input mode3 Phase 4 Wires+ GroundInput voltage(Vac)380V/220V±20%,400V/230V±20%,415V/240V±20%Input Frequency(HZ)50Hz±10%,60Hz±10%Input PF≥0.99Battery voltage(Vdc)±240Charge Time10hs (2hs backup battery capacity)Battery quantity(Pcs)32-48 can be adjustedUPS Power Factor1.0Output Voltage(Vac)380/220V,400/230V,415/240VOutput Frequency(HZ)50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2%60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2%Output voltage Stability±1%(Static);±2%(Load change from 0 ~ 100% ) Efficiency (AC mode @ full loads)≥94%Output voltage recovery time