The automatic extinguisher control panel is designed in accordance
with European standards EN54-2 and EN54-4 Fire Detection and Fire
Alarm systems - Control and Indicating Equipment and EN12094-1
Fixed firefighting systems - Components for gas extinguishing
systems - Part 1: Requirements and test methods for electrical
automatic control and delay devices.The control equipment is a
combined fire alarm control panel and extinguishing system and has
four detection zones, any or all of which are capable of
contributing to the extinguishant release decision.Control panels
have an integral, mains powered battery charger and power supply
designed in accordance with the requirements of EN54-4.In addition
to the requirements of EN54-2 the control panel has the following
facilities:Test condition to allow the automatic resetting of
zones in alarm for testing purposes. EN54-2 Section 10 option with
requirementsDelay of the actioning of fire alarm devices
(sounders) so that an alarm may be verified before a premises is
evacuated. EN54-2 Section 7.11 option with requirements.Fire alarm
devices to enable an audible warning to be sounded throughout
premises upon the detection of a fire condition or the operation of
a manual call point. EN54-2 Section 7.8 option with
requirementsIn addition to the requirements of EN54-2, all control
panels have voltage free relay contacts for fire and local fire
which operate upon a fire condition. These are to be used for local
control and signaling.In addition to the requirements of EN12094-1
the control panel has the following facilities:Delay of
extinguishing signal of up to 75 seconds. EN12094-1
Section 4.17 option with requirements.Signal representing the flow
of extinguishing agent to indicate the released condition.
EN12094-1 Section 4.18 option with requirements.Monitoring of the
status of components by way of a low pressure switch input.
EN12094-1 Section 4.19 option with requirements.Emergency
hold device to enable the extinguishant delay time to be
extended. EN12094-1 Section 4.20 option with requirements.Control
of flooding time to deactivate the releasing output after a
set period of time. EN12094-1 Section 4.21 option with
requirements.Manual only mode to disable the release of
extinguishant via automatic detection devices. EN12094-1 Section
4.23 option with requirements.Triggering of equipment outside the
system by way of first and second stage contacts, extract fan
output etc. EN12094-1 Section 4.26 option with
requirementsActivation of alarm devices with different signals to
indicate pre-discharge and released warnings using different
sounds. EN12094-1 Section 4.30 option with requirements.2.
SafetySuppliers of articles for use at work are required under
section 6 of the Health and Safety at Work act 1974 to ensure as
reasonably as is practical that the article will be safe and
without risk to health when properly used.An article is not
regarded as properly used if it is used 'without regard to any
relevant information or advice' relating to its use made available
by the supplier.This product should be installed, commissioned and
maintained by trained service personnel in accordance with the
following:(i)IEE regulations for electrical equipment in
buildings(ii)Codes of practice(iii)Statutory requirements(iv) Any
instructions specifically advised by the manufacturerAccording to
the provisions of the Act you are therefore requested to take such
steps as are necessary to ensure that you make any appropriate
information about this product available to anyone concerned with
its use.This equipment is designed to operate from 230V/50Hz mains
supplies and is of class 1 construction. As such it
must be connected to a protective earthing conductor in the
fixed wiring of the installation and a readily accessible double
pole disconnect device meeting the requirements of EN60950/IEC950
which disconnects live and neutral simultaneously shall be
incorporated in the fixed wiring.Switch disconnect devices such as
MK Sentry 63A or similar are suitable for this.Failure to ensure
that all conductive accessible parts of this equipment are
adequately bonded to the protective earth will render the equipment
unsafe.This control panel is environmental class A and is designed
for indoor use only at temperatures between -50ºC(+/- 3) and
+400ºC (+/- 2) and with a maximum relative humidity of 95%.The
IP rating for the enclosure is IP30.Operation outside of these
limits may render the equipment unsafe.Conventional Fire Fighting
PanelKey Specifications/Special FeaturesFour Style B (Class B)
Initiating Device Circuits (IDCs).All zones accept two-wire smoke
detectors and any normally-open contact devices.One built-in Fire
Fighting Ouput.24-volt operation.Resettable four-wire smoke
detector power @ 500 mA.Non-resettable power @ 500 mA.One-man
walk-test programmable for silent or audible test.Disable/Enable
control per IDC.Reverse polarity protection. /*
January 22, 2024 19:08:37 */!function(){func
Related products about FM200 Fire Suppression Fire Alarm System with Fire Extinguishant Control Panel
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup